Technical data
Chapter 9 – Communications
Siemens Building Technologies, Inc. 89
Table 11. N2 Point Map.
On Text Off
Text
Point
Number
Name Default
Value
Units Notes
Or Range
SED2 Ref.
AI13 PID SETP OUT 0 PCT No Override -100.0 to 100.0 r2250
AI14 PID OUTPUT 0 PCT No Override -100.0 to 100.0 r2294
AI15 ACTUAL PWR 0 KW No Override 0 to 327.67 r0032
AI16 TOTAL KWH 0 KWH No Override 0 to 32767 r0039
AI17 FREQ ACTUAL 0 PCT No Override -100.00 to 100.00 HIW
AO1 FREQ REF 0 PCT 0.00 to 100.00 HSW
BI1 ENABLED 0 -- No Override ON OFF ZSW:0
BI2 READY TO RUN 0 -- No Override READY OFF ZSW:1
BI3 STOP RUN 0 -- No Override RUN STOP ZSW:2
BI4 AT MAX FREQ 0 -- No Override MAX NO ZSW:10
BI5 CONTROL MODE 1 -- No Override SERIAL LOCAL ZSW:9
BI6 FAULT 0 -- No Override FAULT OK ZSW:3
BI7 WARNING 0 -- No Override WARN OK ZSW:7
BI8 DIGITAL IN 1 0 -- No Override ON OFF r0722:0
BI9 DIGITAL IN 2 0 -- No Override ON OFF r0722:1
BI10 DIGITAL IN 3 0 -- No Override ON OFF r0722:2
BI11 DIGITAL IN 4 0 -- No Override ON OFF r0722:3
BI12 DIGITAL IN 5 0 -- No Override ON OFF r0722:4
BI13 DIGITAL IN 6 0 -- No Override ON OFF r0722:5
BI14 FWD REV 0 -- No Override FWD REV ZSW:14
BO1 CMD START 0 -- START STOP STW:0
BO2 RUN ENABLE 1 -- ENABLE OFF STW:3
BO3 FAULT ACK 0 -- ON OFF STW:7
BO4 HAND AUTO 0 -- HAND AUTO P0718
BO5 DIGITAL OUT 1 0 -- ON OFF P0731
BO6 DIGITAL OUT 2 0 -- ON OFF P0733
BO7 CMD FWD REV 0 -- REV FWD STW:11
BO8 ENABLE PID 0 -- ON OFF P2200
ADF1 ACCEL TIME 1 10.00 SEC 0.00 to 650.00 P1120
ADF2 DECEL TIME 1 10.00 SEC 0.00 to 650.00 P1121
ADF3 CURRENT LMT 150.0 PCT 10.0 to 400.0 P0640