Technical data

Appendix A: Parameter Reference List
Siemens Building Technologies, Inc. 91
Appendix A: Parameter Reference List
P0004 Parameter Filters/Categories
Quick Commissioning (P0010=1)
Parameter
Description Unit
User
Setting
Min Default Max
Access
Level
r0000 Drive display (defined in
P0005)
- - - - X
P0003 User access level to
parameters
- 0 1 4 1
P0010 Commissioning parameter
filter
- 0 0 30 1
P0100 Europe/North America power
settings [kW or hp]
- 0 0 2 1
P0304 Rated motor voltage V 10 230 2000 1
P0305 Rated motor current A 0.01 3.25 10000.00 1
P0307 Rated motor power - 0.01 0.75 2000.00 1
P0308 Rated motor cosPhi - 0.000 0.000 1.000 2
P0309 Rated motor efficiency % 0.0 0.0 99.9 2
P0310 Rated motor frequency Hz 12.00 50.00 or 60.00
650.00 1
P0311 Rated motor speed 1/min 0 0 40000 1
P0640 Motor overload factor [%] % 10.0 150.0 400.0 2
P0700 Selection of command source - 0 2 6 1
P1000 Selection of frequency
setpoint
- 0 2 77 1
P1080 Min. Frequency Hz 0.00 0.00 650.00 1
P1082 Max. Frequency Hz 0.00 50.00 650.00 1
P1120 Ramp-up time s 0.00 10.00 650.00 1
P1121 Ramp-down time s 0.00 10.00 650.00 1
P3900 End of quick commissioning - 0 0 3 1
Inverter Unit (P0004=2)
Parameter
Description Unit
User
Setting
Min Default Max
Access
Level
r0000 Drive display (defined in
P0005)
- - - - X
P0003 User access level to
parameters
- 0 1 4 1
P0004 Parameter filter - 0 0 22 1
P0010 Commissioning parameter
filter
- 0 0 30 1
r0018 Firmware version - - - - 1
r0026 CO: Act. DC link output
voltage
V - - - 2
r0039 CO: Energy consumption
meter
kWh - - - 2
P0040 Reset energy consumption
meter
- 0 0 1 2
r0200 Act. power stack code number
- - - - 3
r0206 Rated inverter power [kW]/[hp]
- - - - 2
r0207 Rated inverter current A - - - 2
r0208 Rated inverter voltage V - - - 2
r0209 Maximum inverter current A - - - 2
P1800 Pulse frequency kHz 2 4 16 2
r1801 CO: Act. switching frequency kHz - - - 3