‘SET’ Series Strobes and Strobe Plates
2581
s Industry, Inc.
Building Technologies Division
s
Data Sheet
Fire Safety Products
Notification Appliances
SET Speakers and Speaker Strobes
Application:
I
ndoor / Outdoor
Product Overview
Fast installation with In / Out screw terminals using
#
12 to
#
18 AWG wires
High-efficiency design for maximum output at minimum wattage
across a frequency range of 400 to 4000Hz
Field-selectable taps for 25 or 70 VRMS operation from 1/8 Watt to 8 Watts
Strobes can be synchronized using the Siemens DSC sync modules;
the Siemens 50-point, 252-point and 504-point fire alarm control panels (FACPs), as well as with:
FireFinder® XLS and MXL® FACPs
PAD-3 or PAD-4™ NAC Extenders with built-in sync protocol
Ceiling-mount models are available with field-selectable Candela settings of
15/30/75/95cd or 115/177cd
Wall-mount models are available with field-selectable Candela settings of
15/30/75/110cd or 135/185cd (multi-Candela models)
Weatherproof (single-candela) models are available with the following ratings:
30/180cd (ceiling or wall mount), per UL 1971
115cd (ceiling or wall mount), per
UL 1638
177cd (ceiling-only mount) per UL 1971
75cd (ceiling-only mount), per
UL 1638
185cd (wall-only mount), per UL 1971
90cd (wall-only mount), per
UL 1638
UL Listed;
FM, CSFM and NYCFD Approved
CSFM (
#
7125-0067:0254 > Fire Alarm Devices For The Hearing Impaired)
CSFM (
#
7125-0067:0255 –> Speakers)
ADA / NFPA compliant
Specifications
Speaker appliances are Siemens Series `SETSpeakers and speaker / strobe appliances
are Siemens Series `SETSpeaker Strobes or approved equals
speakers are UL Listed under Standard 1480 for Fire Protective Service
speaker-strobes are UL Listed under Standard 1971 for Emergency Devices for the Hearing-Impaired
speaker-strobes are UL Listed under Standard 1638 for Weatherproof Devices
Selector switch for selecting the candela is tamper-resistant
SET-MC-CW
Speaker Strobe
SET-CW
Speaker
SET-W
Speaker
SET-MC-R
Speaker Strobe

Summary of content (4 pages)