Technical data

Configuring time synchronization
5.8 Configuring time synchronization on an AS
Time synchronization (V7.1)
Function Manual, 03/2009, A5E01216578-01
101
Setting CP 443-1 (Industrial Ethernet)
To configure time synchronization for the CP443-1, proceed as follows:
1. Open the project in SIMATIC Manager.
2. Select the station that will be synchronized.
3. Open the configuration of the hardware.
4. Select the CP 443-1, followed by Edit > Object Properties.
The "Properties - CP 433-1" dialog box opens.
5. Switch to the "Time-of-Day Synchronization" tab.
6. Activate the "Forward time" check box in the "SIMATIC mode" group.
Note
These settings are available for older versions of the CP 443-1 (<EX11) on the "Options"
tab under "Switch on time synchronization".
7. Click "OK".
If you are operating with several SIMATIC 400 stations, repeat this procedure for each CP.