Technical data

Configuring time synchronization
5.10 Configuring time synchronization with multiple networks
Time synchronization (V7.1)
118 Function Manual, 03/2009, A5E01216578-01
5.10.2 How to configure SCALANCE X414-3E for the separation of time signals
Requirements
The IP address or the URL of the switch must be known.
Requirements for configuration using web-based management must have been met.
Procedure
1. Open Internet Explorer.
2. Enter the IP address or the URL of the switch in the address field of Internet Explorer.
The login dialog of web-based management is displayed once a reliable connection has
been established to the switch.
3. Select the "Admin" entry in the "LoginID" selection field if you wish to edit the settings of
the IE switch (read and write access). You are only granted read access to the
configuration data of the switch if you selected the "User" entry.
4. Enter your password. The default passwords (from the delivery condition) apply if you
have not yet specified a password:
User name: admin - Password: admin
User name: user - Password: user
Note
You are strongly advised to change the default passwords (using the Command Line
Interface - CLI) for security reasons.
5. Click "OK" to initiate login at the switch.
6. Select the "Switch > Ports" folder from the tree view.
The "Port Status" menu opens.
7. In the "Port" column, click the number of the port to which part of the plant is connected.
The "Port Configuration" menu opens.
8. Activate the "Port enabled" check box.
9. Click the "Set Values" button.
10. Connect the networks to the switch.
11. Click "Port".
12. Repeat steps 9 to 11 for the ports of the other plants.