Technical data
Fundamentals
2.8 Network environment of a PCS 7 plant
Time synchronization (V7.1)
Function Manual, 03/2009, A5E01216578-01
27
2.8.3 Network environment within a domain
Central plant clock
The SICLOCK TC 400 is particularly suitable for operation as a central plant clock within a
domain, as the SICLOCK has four independent Ethernet interfaces.
Structure
The following figure illustrates the recommended configuration for a PCS 7 plant in a
Windows domain with a central time clock:
6,&/2&.
'&
$6 $6
0
26FOLHQWV
26VHUYHU
7HUPLQDOEXV
3ODQWEXV
Time synchronization in a domain
The time is synchronized within a domain as follows:
● Time synchronization via plant bus
The plant bus is synchronized using the SICLOCK TC 400.
The synchronization mode depends on the CPU type used (with/without integrated
Ethernet interface).
● Time synchronization via terminal bus
The domain controllers are synchronized directly by the central plant clock using NTP
mode.
The domain controllers synchronize all domain members using the NTP method.