Technical data

Fundamentals
2.8 Network environment of a PCS 7 plant
Time synchronization (V7.1)
Function Manual, 03/2009, A5E01216578-01
27
2.8.3 Network environment within a domain
Central plant clock
The SICLOCK TC 400 is particularly suitable for operation as a central plant clock within a
domain, as the SICLOCK has four independent Ethernet interfaces.
Structure
The following figure illustrates the recommended configuration for a PCS 7 plant in a
Windows domain with a central time clock:
6,&/2&.
'&
$6 $6
0
26FOLHQWV
26VHUYHU
7HUPLQDOEXV
3ODQWEXV
Time synchronization in a domain
The time is synchronized within a domain as follows:
Time synchronization via plant bus
The plant bus is synchronized using the SICLOCK TC 400.
The synchronization mode depends on the CPU type used (with/without integrated
Ethernet interface).
Time synchronization via terminal bus
The domain controllers are synchronized directly by the central plant clock using NTP
mode.
The domain controllers synchronize all domain members using the NTP method.