Technical data
Configuring time synchronization
5.4 Commissioning a central plant clock
Time synchronization (V7.1)
Function Manual, 03/2009, A5E01216578-01
61
Set the basic parameters on the SICLOCK TC 400
The direct parameter settings on the SICLOCK TC 400 are required as basic parameters for
connection to the network only.
1. Press the "Setup" button on the SICLOCK TC 400.
2. Enter the password and then press "OK".
The parameter list is displayed:
– Language (select German or English)
– ETH1 IP address
– ETH1 IP subnet
– ETH1 IP gateway
– ETH2 IP address
– ETH2 IP subnet
– ETH2 IP gateway
– ETH3 IP address
– ETH3 IP subnet
– ETH3 IP gateway
– ETH4 IP address
– ETH4 IP subnet
– ETH4 IP gateway
– Acknowledge events
– Version (for information only)
3. Perform the settings for the required Ethernet connections.