Technical data

Configuring time synchronization
5.5 Configuring the time synchronization of the OS
Time synchronization (V7.1)
Function Manual, 03/2009, A5E01216578-01
77
Result
The communication module can send and receive the time message frames. The OS
servers are cooperative time masters. If a communications processor (CP1613, CP 1623)
does not receive a time signal on the plant bus, WinCC time synchronization automatically
switches to master mode. It will then send substitute time signals for the failed time master.
CAUTION
If a time jump of more than 5 seconds occurs, the computer defined as the time master
becomes a time slave. The message "Time synchronization has been permanently
switched to slave" is generated.
Note that also after a restart this computer is no longer defined as time master. Reconfigure
the computer as time master and load the configuration on the computer.