Technical data

Configuring time synchronization
5.5 Configuring the time synchronization of the OS
Time synchronization (V7.1)
Function Manual, 03/2009, A5E01216578-01
79
5.5.4 How to set time synchronization on an OS in a domain with central time master
Example configuration
The SICLOCK TC 400 central plant clock is used in a Windows domain for time synchronize
of the OS.
'& '&
(QJLQHHULQJ
6WDWLRQ
$6 $6
26FOLHQWV %$7&+VWDWLRQ
26VHUYHU 26VHUYHU
7HUPLQDOEXV
3ODQWEXV
6,&/2&.
0
0
Requirements
All operator stations must be installed in one domain.
The SICLOCK TC 400 must be connected to the terminal bus and the plant bus.
For the CP of the OS server the "Time tracking" option is selected in NetPro.
The OS server must be equipped with a communication module:
CP 1613 or CP 1623 (more than 8 AS or high-availability AS)
BCE (up to 8 AS)
All automation systems must be configured as time slaves (exceptions: CPU 416-3
PN/DP, CPU 414-3 PN/DP).