Technical data

Configuring time synchronization
5.5 Configuring the time synchronization of the OS
Time synchronization (V7.1)
Function Manual, 03/2009, A5E01216578-01
89
Rules
Note
The automation system can only be synchronized if at least one OS server is activated.
CAUTION
If a time jump of more than 5 seconds takes place on the OS server in the UTC, then the
OS server configured as time master will no longer be used as time master. In addition the
I&C system message "Time synchronization has been permanently deactivated" will be
output.
Note that also after a restart this server is no longer defined as time master. Reconfigure
the OS server as time master and load the configuration on the OS server.