6.3 Stationary danger zone guarding
Pic. 6.7: Safety Sensor activates the stop and, with protective field with rear area
protection, performs a presence-detecting function.
Procedure
ª Determine the height of the beam level.
ª Calculate the necessary safety distance and determine the required additional
distances for your application.
ª Define the protective field limits and the warning field limits if required.
ª Configure the protective field so that the safety-related switching outputs are
switched off from every accessible point with sufficient minimum distance "D".
ª Mark the protective field limits on the floor.
You can easily test the Safety Sensor along this marking.