Installation manual
Networking
5-28
S7-400 and M7-400 Programmable Controllers Hardware and Installation
A5E00069481-04
Table 5-4 Features of the Fiber-Optic Cables, continued
Description
SIMATIC NET PROFIBUS
Plastic Fiber-Optic
Duplex Conductor
Plastic Fiber-Optic
Standard Cable
PCF Fiber-Optic
Standard Cable
Resistance to lateral pressure
per 10 cm cable length
(short-term)
35 N/ 10 cm 100 N/ 10 cm 750 N/ 10 cm
Bend radii
• Single bend
(without tensile force)
• Multiple bends
(with tensile force)
30 mm
50 mm
(flat side only)
100 mm
150 mm
75 mm
75 mm
Permissible environmental
conditions
• Transport/storage
temperature
• Laying temperature
• Operating temperature
-30 _C to +70 C
0 C to +50 C
-30 C to +70 C
-30 C to +70 C
0 C to +50 C
-30 C to +70 C
-30 C to +70 C
-5 C to +50 C
-20 C to +70 C
Resistance against
• Mineral oil ASTM no. 2,
grease or water
• UV radiation
Conditional
1
)
Not UV-resistant
Conditional
1
)
Conditional
1)
Conditional
1
)
Conditional
1
)
Flame retardance Flame retardant in accordance with the VW-1 flame test to UL 1581
External dimensions 2.2 4.4 mm
0.01 mm
Diameter:
7.8 0.3 mm
Diameter:
4.7 0.3 mm
Weight 7.8 kg/km 65 kg/km 22 kg/km
1