S7-400 and M7-400 Programmable Controllers Hardware and Installation
A5E00069481-04
Table 5-4 Features of the Fiber-Optic Cables, continued
Description
SIMATIC NET PROFIBUS
Plastic Fiber-Optic
Duplex Conductor
Plastic Fiber-Optic
Standard Cable
PCF Fiber-Optic
Standard Cable
Resistance to lateral pressure
per 10 cm cable length
(short-term)
35 N/ 10 cm 100 N/ 10 cm 750 N/ 10 cm
Bend radii
Single bend
(without tensile force)
Multiple bends
(with tensile force)
30 mm
50 mm
(flat side only)
100 mm
150 mm
75 mm
75 mm
Permissible environmental
conditions
Transport/storage
temperature
Laying temperature
Operating temperature
-30 _C to +70 C
0 C to +50 C
-30 C to +70 C
-30 C to +70 C
0 C to +50 C
-30 C to +70 C
-30 C to +70 C
-5 C to +50 C
-20 C to +70 C
Resistance against
Mineral oil ASTM no. 2,
grease or water
UV radiation
Conditional
1
)
Not UV-resistant
Conditional
1
)
Conditional
1)
Conditional
1
)
Conditional
1
)
Flame retardance Flame retardant in accordance with the VW-1 flame test to UL 1581
External dimensions 2.2 4.4 mm
0.01 mm
Diameter:
7.8 0.3 mm
Diameter:
4.7 0.3 mm
Weight 7.8 kg/km 65 kg/km 22 kg/km
1