Installation manual

Assembling and Installing Systems
A-27
S7-400 and M7-400 Programmable Controllers Hardware and Installation
A5E00069481-04
Low-Voltage Protection Elements for 2<> 3
For the transition points between lightning protection zones 2 <> 3 we
recommend the surge protection components listed in the table below. This
low-voltage protection must be used in S7-400 for CE compliance.
Table A-5 Surge Protection Components for Lightning Protection Zones 2 <> 3
Ser.
No.
Cables for ... ... .. equip transition point
2 <> 3 with:
Order No.
1 3-phase TN-C-System 3 pieces
of
DEHNguard 275 surge arresters 900 600*
5SD7 030
3-phase TN-S system 4 pieces
of
DEHNguard 275 surge arresters 900 600*
5SD7 030
3-phase TT system 3 pieces
of
DEHNguard 275 surge arresters phase
L1/L2/L3 to N
900 600*
5SD7 030
1 piece of DEHNgap C N-PE surge N to PE 900 131*
AC TN-S system 2 pieces
of
DEHNguard 275 surge arresters 900 600*
5SD7 030
AC TN-C system 1 piece of DEHNguard 275 surge arresters 900 600*
5SD7 030
AC TT system 1 piece of DEHNguard 275 surge arresters phase
L to N
900 600*
5SD7 030
1 piece of DEHNgap C N-PE surge N to PE 900 131*
2 24 VDC Power Supply 1 piece of Blitzductor VT lightning conductor, type
AD 24 V
918 402*
3 Bus cable
MPI RS 485 Blitzductor CT surge arrester, type
MD/HF
919 506* and
919 570*
RS 232 (V.24) 1 piece of per conductor pair low-voltage pro-
tection FDK 2 12 V
919 995*
4 Inputs of digital modules
24 VDC 1 piece of Low-voltage surge arrester,
type FDK 2 60 V on insulated rail
919 993*
2 pieces
of
Surge arresters
120 VAC DEHNrail 120 FML 901 101*
230 VAC DEHNrail 230 FML 901 100*
5 Outputs of digital modu-
les 24 VDC
1 piece of Low-voltage protection FDK 2 D 5 24 919 991*
6 Outputs of analog modu-
les up to 12 V +/
1 piece of Low-voltage protection,
type FDK 2 12 V on insulated rail con-
nected with M of the power supply for
the modules.
919 995*