Installation manual

Assembling and Installing Systems
A-36
S7-400 and M7-400 Programmable Controllers Hardware and Installation
A5E00069481-04
!
Caution
There is a risk of personal injury.
Dangerous touch voltages may be present at the video sockets of the monitor.
Fit suitable touch protection to the sockets.
Connect the ground clamp of the monitor to the chassis ground.
Connect the cable shields to the ground clamp of the monitor as follows:
Proceed as follows:
Strip the outer cable insulation of the video cables in the region of the ground
clamp of the monitor, without damaging the braided shield.
Secure the outer braided shield over a large area to the ground clamp of the
monitor.
Figure A-11 shows a simplified representation of shielding and grounding for
monitor and S7-400.
CR
CP
Shield bus
Outer shield
connected
to ground
clamp
Monitor with
separate
electronic
ground and
housing
ground
Figure A-11 Shielding and Grounding with a Great Distance between Monitor and Programmable
Controller