General data
Operating voltage DC 18 to 32 V safety extra-low voltage (SELV) (redundant inputs decoupled)
Current consumption typ. 160 mA (OLM) respectively 80 mA (ELM) at 24 VDC (without AUI-load)
max. 280 mA (OLM) respectively 430 mA (ELM) at 24 VDC (with AUI-load)
Overload current protection at input non-changeable thermal fuse
Dimensions W x H x D 80 mm x 140 mm x 85 mm
Mass OLM 900 g, ELM 850 g
Ambient temperature 0 ºC to + 60 ºC
Storage temperature - 40 ºC to + 80 ºC
Humidity 10% to 90% (not-condensing)
Protection class IP 30 (OLM), IP 40 (ELM)
Radio interference level EN 55022 Class B
Interference immunity EN 50082-2
Network size
Transition ITP-Port ITP-Port (OLM, ELM) F/O port F/O port (OLM)
Propagation equivalent 190 m 260 m
Variability Value 3 BT 3 BT
Transition ITP-Port F/O port (OLM) ITP-Port AUI-Port (ELM)
Propagation equivalent 360 m 190 m
Variability Value 6 BT 3 BT
F/O port (OLM OLM)
Optical output power
Graded-index fiber 50/125 µm (average) min. -22,0 dBm max. -16,2 dBm
Graded-index fiber 62,5/125 µm (average) min. -19,0 dBm max. -12,4 dBm
Optical input power min. -33,0 dBm
ITP line length (ITP-Port ITP-Port)
Length of an industrial twisted pair segment max. 100 m
AUI line length (AUI-Port AUI-Port)
Length of an AUI cable max. 50 m
F/O line length (example)
50/125 µm fiber max. 2.600 m
62,5/125 µm fiber max. 3.100 m
Scope of delivery
SIMATIC NET Industrial Ethernet
OLM V2.0/ELM incl.
terminal block for supply voltage
description and operating instructions
Order number
SIMATIC NET Industrial Ethernet OLM V2.0 6GK1102-4AA00
SIMATIC NET Industrial Ethernet ELM 6GK1102-5AA00
Accessories
“Industrial Twisted Pair Networks” manual 6GK1970-1BA00-0AA0
Ethernet manual HIR:943 320-011
Notes on CE identification
The link modules for Industrial
Ethernet comply with the regulati-
ons of the following European
directive:
89/336/EEC
Council Directive on the harmoni-
sation of the legal regulations of
member states on electromagnetic
compatibility (amended by Direc-
tives 91/263/EEC, 92/31/EEC and
93/68/EEC).
Area used Requirements for
emitted interference interference immunity
Residential EN 50081-1: 1992 EN 50082-1: 1992
Industrial EN 50081-2: 1993 EN 50082-2: 1995
The product can be used in the residential
sphere (residential sphere, business and
trade sphere and small companies) and in
the industrial sphere.
The precondition for compliance with EMC
limit values is strict adherence to the con-
struction guidelines specified in this
description and operating instructions and
in the “Industrial Twisted Pair Networks”
manual!
The EU declaration of conformity is kept
available for the responsible authorities in
accordance with the above-mentioned EU
directives at:
Siemens Aktiengesellschaft
Bereich Automatisierungs- und
Antriebstechnik
Industrielle Kommunikation (A&D PT2)
Postfach 4848
D-90327 Nürnberg
737 211-002-01-0298