Technical data

Command Interface
5-29
SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02
5.2.16 Get_LPS, Get_LAS, Get_LDS, Get_Flags
Purpose
With this call, the following entries are read out of the AS-i master CP 243-2:
The list of active AS-i slaves (LAS)
The list of detected AS-i slaves (LDS)
The list of permanent AS-i slaves (LPS)
The flags according to the AS-i specification
Structure of the Job Data in the Send Buffer
Bank Byte Meaning
2 0 Command number: 30
H
Structure of the Job Data in the Receive Buffer
Bank Byte Meaning
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
2 0
30H
2 1 Command status
2 2 LAS
slave 0
LAS
slave 1
LAS
slave 2
LAS
slave 3
LAS
slave 4
LAS
slave 5
LAS
slave 6
LAS
slave 7
2 3 LAS
slave 8
LAS
slave 9
LAS
slave 10
LAS
slave 11
LAS
slave 12
LAS
slave 13
LAS
slave 14
LAS
slave 15
2 4 LAS
slave 16
LAS
slave 17
LAS
slave 18
LAS
slave 19
LAS
slave 20
LAS
slave 21
LAS
slave 22
LAS
slave 23
2 5 LAS
slave 24
LAS
slave 25
LAS
slave 26
LAS
slave 27
LAS
slave 28
LAS
slave 29
LAS
slave 30
LAS
slave 31
2 6 reserv. LAS
slave 1B
LAS
slave 2B
LAS
slave 3B
LAS
slave 4B
LAS
slave 5B
LAS
slave 6B
LAS
slave 7B
2 7 LAS
slave 8B
LAS
slave 9B
LAS
slave
10B
LAS
slave
11B
LAS
slave
12B
LAS
slave
13B
LAS
slave
14B
LAS
slave
15B
2 8 LAS
slave
16B
LAS
slave
17B
LAS
slave
18B
LAS
slave
19B
LAS
slave
20B
LAS
slave
21B
LAS
slave
22B
LAS
slave
23B
2 9 LAS
slave
24B
LAS
slave
25B
LAS
slave
26B
LAS
slave
27B
LAS
slave
28B
LAS
slave
29B
LAS
slave
30B
LAS
slave
31B
2 10 LDS
slave 0
LDS
slave 1
LDS
slave 2
LDS
slave 3
LDS
slave 4
LDS
slave 5
LDS
slave 6
LDS