User manual

Diagnostic T
ests and T
roubleshooting
5-7
T
able 5-1
Peerlink T
roubleshooting Chart (Continued)
Symptom
Possible Problem
Solution
Module
passes
If you have pressed
This is normal. It
power
-up test;
RESET
, it may take
may take the P/C COMM
MODULE
the module several
GOOD indicator a few
GOOD light
scans to log itself
seconds to light.
is on, but P/C
back in.
COMM GOOD
does not come
on for several
seconds.
P/C COMM
The Peerlink module Move Peerlink to
GOOD
may be in a distributed
the local base.
indicator stays
base. It should
Set the appropriate
off.
be in the local I/O
V Memory output
base.
words (WYs) for the
new slot location.
or or
Module not logged
Log in the Peerlink
into I/O configuration
module.
table.
MODULE
Peerlink station has
Check dipswitch
GOOD,
the same address as
settings for network
RECEIVE, and
the active monitor
.
address; change as
P/C COMM
necessary.
GOOD light,
but
TRANSMIT
stays off.
TRANSMIT or
Excessive communication
Check that terminating
RECEIVE
errors are occurring
resistors are installed
indicators
because of an
properly
. See page 3-13
flash.
improperly terminated
of this manual
line.
Module
No network Check to see that
GOOD and
communication is taking
all modules are
P/C COMM
place.
connected correctly
,
indicators are
that station numbers
on; all others
are unique, and that
are off.
exactly one module is
selected as the
active monitor
.