Computer Drive Installation Instructions

12 Functional Descriptions 04.96
12.20 Extended stop and retract (ESR) (SW 4 and higher)
Application of internal sources:
- Emergency retraction threshold FA/FS,
- 611D DC link voltage threshold, drive MD 1634,
- 611D generator speed threshold, drive MD 1635
which must initiate a retraction operation.
Definition of internal reactions to be initiated in the case of a retraction operation:
- Alarm and mode group stop
- Retraction operation as open-loop control function and/or as
- Autonomous drive function
Drive parameters for the "Extended stop and retract" function (611D)
DC link voltage threshold, drive MD 1631: If the voltage drops below this limit, a
drive defined as the generator axis switches to generator mode.
Voltage step, drive MD 1632: This value defines the upper threshold of the two-
position controller for generator operation.
DC link voltage threshold, drive MD 1633: If the voltage exceeds this limit value,
the drive switches from generator mode back to normal operation.
DC link voltage threshold, drive MD 1634: If the voltage drops below this limit,
emergency retraction measures can be initiated according to user specifications
(via MD or programming).
Generator speed threshold, drive MD 1635: If the speed drops below this value,
emergency retraction measures can be initiated according to user specifications
(via MD or programming).
2.) The possibility of controlling the function via the PLC:
Channel-specific
To PLC:
- ESR monitoring is active
- ESR reaction is initiated
Axis/spindle-specific
From PLC:
- Activate ESR monitoring
- Disable ESR monitoring
- Enable ESR reaction
To PLC:
- ESR monitoring is active
- ESR reaction is initiated
- ESR reaction is programmed
- 611D ZK2 messages
If monitoring is switched on from the PLC, it can be switched off from the PLC only.
If monitoring is switched off from the PLC, it is switched off for all channels.
12–214