Specifications

SINAMICS G150 NEMA
Type A enclosed drive
2
Siemens D11.7 (Part 1) – 2013
2/12 2/13
Description of options
M90
Lifting beam/eye bolts
Note: Option M90 is strongly recommended, to enable
lifting the drives off their pallet safely.
For single cabinets up to a width of 24” (600 mm), eye bolts
are provided. For larger enclosures transportation beams
are provided.
Once the drives are in position, the lifting hardware needs to
be removed to mount the tophats. For multiple drives with
identical enclosure sizes, option M90 can be ordered once
and the hardware re-used for other units.
SINAMICS G150 type A on pallet with transportation beams
N55
ALL STOP, coast to stop
A mushroom style, latching, twist-to-release, padlockable
push button is mounted on the door wired to OFF2. The
motor coasts to stop.
This function is a basic single channel stop circuit. With an
input contactor (options L13, L29 or L30), the drive can also
be isolated from the supply.
N57
EMERGENCY OFF category 0, coast to stop, 120 V AC
or 24 V DC
EMERGENCY OFF Category 0 for uncontrolled stop in
accordance with IEC 60204-1
The function bypasses the microprocessor controller by
means of a safety relay combination in accordance with
IEC 60204-1, and disconnects the drive from the line by
opening the input contactor. The motor coasts to stop.
A mushroom style, latching, twist-to-release, padlockable
push button is mounted on the door. When delivered, the
button circuit is preset to 120 V AC. Jumpers must be set
when using 24 V DC.
N59
EMERGENCY STOP category 1, controlled ramp down,
120 V AC
EMERGENCY STOP Category 1 for controlled stop in
accordance with IEC 60204-1, 120 V AC circuit.
The function includes a fast ramp down of the drive (to be
parameterized by the user). This is followed by disconnecting
the drive from the supply as described for the EMERGENCY
OFF category 0.
A mushroom style, latching, twist-to-release, padlockable
push button is mounted on the door.
A braking unit may be necessary to achieve the required
shutdown times.
Attention: Option N59 always assumes that the drive can be
electrically isolated from the supply; i.e. either option L13,
L29 or L30 must be selected too.
N60
EMERGENCY STOP category 1, controlled ramp down,
24 V DC
EMERGENCY STOP Category 1 for controlled stop in
accordance with IEC 60204-1, 24 V DC circuit.
The function includes a fast ramp down of the drive (to be
parameterized by the user). This is followed by disconnecting
the drive from the supply as described for the EMERGENCY
OFF category 0.
A mushroom style, latching, twist-to-release, padlockable
push button is mounted on the door.
A braking unit may be necessary to achieve the required
shutdown times.
Attention: Option N60 always assumes that the drive can be
electrically isolated from the supply; i.e. either option L13,
L29 or L30 must be selected too.
N70
Control power supply 120 V, 6 A
A 120 V 1ph. AC control power supply fused for 6A,
protected by an MCP, is provided for customer use, for
example to supply power to external interlocking circuits.