Specifications

SINAMICS G150 NEMA
Type C enclosed chassis
3
Siemens D11.7 (Part 1) – 2013
3/11
Line side components for SINAMICS G150 NEMA type C enclosed chassis
SINAMICS G10 NEMA type C enclosed chassis do not include
any line side components (except for the optional line
reactor) – these components need to be added externally,
for example in an MCC.
To obtain the drive SCCR (short circuit current ratings) shown
in the technical data, it is necessary to combine it with the
fuses and fuse bases listed in the manual, and shown in the
table below (substitutes are not permitted). Also, a UL-listed
circuit breaker for motor branch circuit protection (with
minimum SCCR as required for the drive) is required, which
may not exceed the maximum current rating shown.
The SCCR shown below is the value applicable to the
drive when combined with the specified fuses, and the
recommended circuit breaker and, if applicable,
recommended contactor (used as input, output and/or
bypass contactor).
SINAMICS G150
NEMA Type C
Enclosed chassis
Output
(light overload)
at 460 V or
575 V, 60 Hz
Circuit breaker Semiconductor fuses Contactor
max.
rating
Recommended
part #
SCCR
max.
1)
Fuse
required
part #
Fuse base
required
part #
Recommended
part #
SCCR
max
1) 2)
Model No. HP A kA per phase per phase Siemens kA
Supply voltage 380 V to 480 V 3 ph. AC
6SL3710-1GE32-1CU3 150 500
HJX3B300 65
3NE12302 3NH3320
3RT10666AF36 65
6SL3710-1GE32-6CU3 200 600
HJX3B400 65
3NE13312 3NH3320
3RT10766AF36 65
6SL3710-1GE33-1CU3 250 700
HLX3B500 65
3NE13342 3NH3420
3RT10766AF36 65
6SL3710-1GE33-8CU3 300 800
HLX3B600 65
3NE13342 3NH3420
3RT10766AF36 65
6SL3710-1GE35-0CU3 400 1200
HMX3B800 65
3NE14362 3NH3420
3RT10766AF36 65
6SL3710-1GE36-1CU3 500 1200
HMX3B800 65
3NE14382 3NH3420
40NH32AF 65
6SL3710-1GE37-5CU3 600 1600
HNX3X100 65
3NE14482 3NH3420
40NH32AF 65
6SL3710-1GE38-4CU3 700 2000
HNX3X120 65
2x 3NE14362 2x 3NH3420
40PH32AF 65
6SL3710-1GE41-0CU3 800 2000
HPX3X160 65
2x 3NE14372 2x 3NH3420
40PH32AF 65
Supply voltage 500 V to 600 V 3 ph. AC
6SL3710-1GF31-8CU3 150 400
HJX3B300 25
3NE12272 3NH3320
3RT10666AF36 25
6SL3710-1GF32-2CU3 200 500
HJX3B350 25
3NE12302 3NH3320
3RT10666AF36 25
6SL3710-1GF32-6CU3 250 600
HJX3B350 25
3NE13312 3NH3320
3RT10666AF36 25
6SL3710-1GF33-3CU3 300 800
HLX3B500 25
3NE13342 3NH3420
3RT10766AF36 25
6SL3710-1GF34-1CU3 400 1000
HLX3B600 25
3NE13342 3NH3420
3RT10766AF36 25
6SL3710-1GF34-7CU3 450 1000
HMX3B800 35
3NE14352 3NH3420
3RT10766AF36 30
6SL3710-1GF35-8CU3 600 1200
HMX3B800 35
3NE14472 3NH3420
40NH32AF 35
6SL3710-1GF37-4CU3 700 1600
HNX3X100 35
3NE14482 3NH3420
40PH32AF 35
6SL3710-1GF38-1CU3 800 2000
HNX3X120 35
2x 3NE13342 2x 3NH3420
40PH32AF 35
1) The short circuit current ratings (SCCR) listed above are the SCCR for the enclosed drive unit when used with the recommended components.
2) The SCCR listed for the contactor is the combination SCCR when the contactor is used in combination with the recommended circuit breaker.
3) The circuit breaker part # is for the circuit breaker frame only, and does not include any accessories required for connection (for example lugs).
NOTE: SCCR ratings are provided for information only, and are based on published catalog data at the time this catalog was written. Since the data may be