Fire Safety & Security Products 05.2010
Smoke detector installation
The mounting of the detector subject to tunnel design is shown in Fig. 17. Where
smok
e or exhaust ducts are installed. It is NOT advisable to install detectors within
the duct due to; If the ventilation (fan) is switched off then smoke will not be drawn
in to the duct to allow detection of any smoke particles.
Fig. 17 Top and on the wall smoke detector installation
With the installation type’s principle, two variants can be used: ring (class A) or star
(class B) wiring. To optimize the cost factor is star wiring for the Profibus installa-
tion preferred. For ring connection fiber optic cables are used.
Fig. 18 Star wiring: one and two part’s
Fig. 19 Ring wiring: one and two part’s
When installed below ceiling the smoke detector is usually placed 50cm offset (or
according the local regulations) from the tunnel center line, inclusive of mounting
brackets and fall protection. This mounting method allows maintenance on the
smoke detector when a traffic lane is closed.
Distance road to detecto
r
> 5m
> 5m
4.5m
Distance road to detecto
r
> 4.5m