User Manual

Fire Safety and security measures
73
Building Technologies A6V10283843_a_en
Fire Safety & Security Products 05.2010
Gravity operated flaps, this is the option recommended by Siemens:
Fig. 56 Gravity operated flap
Advantage: gravity flaps offer the highest reliability
Disadvantages: medium efficiency, to overcome this, larger flaps need to be cal-
culated to ensure the correct free air space is provided.
…or alternatively they can be operated electrically:
Fig. 57 Electrically operated flap
Of all possible relief flaps, the electrically operated are the less recommended by
Siemens. The reliability of gravity and pneumatic flaps is higher and therefore pre-
ferred.
Important: Some electrically operated flaps open slowly and close very quickly,
but this is the opposite of what is needed for an inert gas discharge!
Possible solution:
The vent must be timed to be fully open by the time that the system discharges
The vent must then be timed to remain open for around 50 to 60 seconds
The vent can then begin to close
Other functions of the system should also be considered Abort /Hold button!!!!
Overpressure flap
Gravity operated
Overpressure flap
Overpressure flap
Electrically operated
Overpressure flap