4. Maintenance guidelines
Leak check:
Cylinders are not pressurised, therefore a leak test is not requied.
If leakages arise during a extinguishing, check the connections and tighten if necessary.
Maintenance instruction:
yearly:
- dismantling the anti evaporation device and check the membranes and o-ring for deterioration
10 years periode:
- replace water and additive
after discharge:
- dismantling the anti evaporation device and replace the membranes and o-ring
with maintenance set S54476-S29-A1 for each water cylinder 1 piece, including
1x CX 884006 / S54476-B29-A1
1x S54476-B243-A1
1x A5Q00038752
- additive refill
with additive 1x FR6:LB570670008 for each water cylinder 1 piece