User Manual

Document ID: 009906_d_en_GB
Edition: 05.2009
4 of 4
Switching on detector zones / detectors (Password required)
When there is no event with a higher priority, isolations (switched off) are directly indicated on the display. You
may then directly proceed with Step 3 below.
When all zones within a section (a zone is a detector in this system’s terminology) are turned off, the section is
additionally indicated as switched off.
Detectors that still contain smoke or test gas cannot be switched back on.
Step Result
1.
Press the button to open the main menu.
(password required)
Press <1> "Message summary".
Message summary
Exit with <C>
Access level 2.1
002
003
Isolations
Information
(4)
(8)
Function
On/Off
Function
All
LED
Test
2.
Press <4> "Isolations".
2007-10-10 15:14:36
002 Isolations
OFF
1/01 Reception
OFF
Ground Floor
Zone no 2
Zone no 2
001
002
Execute
command
Switch to
extended view
More
options
3.
Scroll with the navigation buttons to the
isolation (detector e.g. Reception, or zone
e.g.Ground Floor) you want to switch on.
The selected isolation is marked by a frame.
Press Softkey <1> "Execute command”.
Select command
ON (1)
4.
Press <1> "ON".
Command response confirms the execution.
Detector or zone switched on.
LED "ISOLATION" is off, provided that there is no other
isolation.
Procedure in case of Fault
Step
Result
1.
Press <Silence buzzer> on the PMI.
Buzzer on the station switched off.
2.
Read message/fault location on the display.
Information on type and place of the fault.
3.
Press <Acknowledge> on the PMI.
4.
Go to the fault location and remedy the cause
of the fault.
The fault will clear automatically from the station.
If you cannot eliminate a fault, please contact your service provider.