Operating instructions
Functional safety
8.2 Device-specific safety instructions
SIPART PS2 with and without HART communications
108 Operating Instructions, A5E00074631-09
8.2.2 Safety function
Safety function on positioner
The safety function on the SIPART PS2 positioner is the depressurizing of the connected
valve actuator. The built-in spring brings the valve to the required safety position. Depending
on the direction of action of this spring, the valve is completely opened or closed.
This function is referred to as "tight closing" in the device documentation.
This safety function can be triggered by:
● Failure of auxiliary electrical power
● Falling below failure signal 3.6 mA at set current input (I
w
).
This also applies to failure of the pneumatic auxiliary power.
Note
Partial stroke test
If a partial stroke test is running, the safety function is only triggered if the electrical and
pneumatic power supply is switched off. The safety function is not triggered by an input
current less than 3.6 mA.
If the valve actuator cannot be depressurized on demand or in case of a fault, this represents
a dangerous failure.
WARNING
The binding settings and conditions are listed in the sections "" Settings (Page 109) and
Safety characteristics (Page 110).
These conditions must be
met in order to fulfil the safety function.
When the safety function has been executed, safety-instrumented systems with no self-
locking function should be brought to a monitored or otherwise safe status within the Mean
Time To Restoration (MTTR). The MTTR is 8 hours.
The calculated Mean Time Between Failures (MTBF) for the SIPART PS2 positioner is 90
years. The MTBF for the basic electronics module is 181 years in line with SN29500.
The characteristic service life of the valve block depends on the load. On average it is
approx. 200 million switching operations for each of the two pilot valves with symmetrical
load. The actual number of switching operations performed can be called in the local display
or via HART communication.
See also
Meaning of diagnostics values (Page 187)
Overview of diagnostics values (Page 185)
Chapter 8 is invalid and is replaced by
Compact operating instructions
"Functional Safety SIPART PS2" A5E00442120-04










