Operating instructions
Commissioning
9.2 Commissioning linear actuators
SIPART PS2 with and without HART communications
Operating Instructions, 09/2008, A5E00074631-08
123
5. Call the fourth parameter "INITA". Press the operating mode button for a short while
for this purpose. The following is shown on the digital display:
6. Start the initialization process. The positioner runs through five initialization steps during
the automatic initialization process. Displays for the initialization steps from "RUN 1" to
"RUN 5" are shown in the lower line on the digital display. The initialization process
depends on the actuator used, and takes up to 15 minutes. To start the initialization,
press the increment button
for at least 5 seconds until the digital display shows the
following:
7. The following display indicates that the automatic initialization is complete:
Setting parameter 3
Proceed as follows to set parameter 3:
1. On the scale of the lever, read the value marked by the carrier pin.
2. Set the parameter to the read value. Use the
increment or decrement buttons for
this purpose.
Aborting the automatic initialization process
1. Press the operating mode button. The following is shown on the digital display:
2. Exit the "Configuration" mode. To do this, press the operating mode button
for at least
5 seconds.
3. The software status is displayed.
4. After releasing the
operating mode button, the positioner is in the "P manual mode",
i.e. the positioner has not been initialized.
See also
Sequence of automatic initialization (Page 114)