Operating instructions
Commissioning
9.2 Commissioning linear actuators
SIPART PS2 with and without HART communications
126 Operating Instructions, 09/2008, A5E00074631-08
9. Determine the end position 2 of the actuator spindle. Move the actuator spindle to the
desired position by pressing the
increment or decrement buttons. Accept the
current position of the actuator spindle by pressing the
operating mode button.
Note
"Set Middl" fault message
The lever arm is not in the horizontal position if the "Set Middl" message appears on the
digital display. To correct the fault, set the reference point of the sine correction. Proceed
as follows:
1. Move the lever arm to the horizontal position by pressing the
increment or
decrement buttons.
2. Press the
operating mode button.
10. The initialization process is automatically resumed. Displays for the initialization steps
from "RUN1" to "RUN5" are shown in the lower line on the digital display.
11. The following display indicates that the initialization has been completed successfully:
Note
If the "YWAY" parameter has been set, the digital display shows the total stroke in mm.
Aborting the manual initialization process
1. Press the operating mode button. The digital display shows the "INITM" parameter.
The positioner is in the "Configuration" mode.
2. Exit the "Configuration" mode. To do this, press the operating mode button
for at least
5 seconds.
3. The software status is displayed.
4. After releasing the
operating mode button, the positioner is in the "P manual mode",
i.e. the positioner has not been initialized.