Operating instructions

Parameterizing/addressing
10.3 Overview of parameters
SIPART PS2 with and without HART communications
140 Operating Instructions, 09/2008, A5E00074631-08
Parameter Function Parameter values Unit
A1 = Min, A2 = Max
A1 = Min, A2 = Min
A1 = Max, A2 = Max
45.A1 Trigger threshold, alarm 1 0.0 ... 10.0 ... 100 % %
46.A2 Trigger threshold, alarm 2 0.0 ... 90.0 ... 100 % %
Function for fault message output Normal Inverted
Fault
Fault + not automatic
4)
47. FCT 3)
Fault + not automatic + BE
4)
48. TIM Monitoring time for setting of fault message
"regulation deviation"
Auto / 0 ... 100 s
49. LIM Response threshold for fault message
"regulation deviation"
Auto / 0 ... 100 %
Preset (factory setting)
5)
no Nothing activated no
Strt Start of factory setting Strt
50.PRST
oCAY Display after pushing button for 5 sec oCAY
Activation of extended diagnostics
Off OFF
Single-level message On1
Two-level message On2
51.XDIAG
Three-level message On3
1)
Interpolation points appear only upon selection of 12.SFCT = "FrEE"
Normally closed
means:
Action on switch open or Low level
2)
Normally closed
means:
Action on switch closed or High level
Normal means: High level without fault
3)
Inverse means: Low level without fault
4)
"+" means: Logical OR combination
5)
Preset results in "NOINI"!