Operating instructions
Parameterizing/addressing
10.3 Overview of parameters
SIPART PS2 with and without HART communications
142 Operating Instructions, 09/2008, A5E00074631-08
Overview parameter C
Parameter Function Parameter values Unit
C. LEAK Pneumatic leakage with the following parameters:
C1.LIMIT Limit 0.1 ... 30.0 ... 100.0
C2.FACT1 Factor 1 0.1 ... 1.0 ... 100.0
C3.FACT2 Factor 2 0.1 ... 1.5 ... 100.0
C4.FACT3 Factor 3 0.1 ... 2.0 ... 100.0
%
Overview parameter d
Parameter Function Parameter values Unit
d. STIC Friction (slip-stick effect) with the following parameters:
d1.LIMIT Limit 0.1 ... 1.0 ... 100.0
d2.FACT1 Factor 1 0.1 ... 2.0 ... 100.0
d3.FACT2 Factor 2 0.1 ... 5.0 ... 100.0
d4.FACT3 Factor 3 0.1 ... 10.0 ... 100.0
%
Overview parameter E
Parameter Function Parameter values Unit
E. DEBA Dead zone monitoring with the following parameters:
E1.LEVEL3 Threshold 0.1 ... 2.0 ... 10.0 %
Overview parameter F
Parameter Function Parameter values Unit
F. ZERO Zero point monitoring with the following parameters:
F1.LEVEL1 Threshold 1 0.1 ... 1.0 ... 10.0
F2.LEVEL2 Threshold 2 0.1 ... 2.0 ... 10.0
F3.LEVEL3 Threshold 3 0.1 ... 4.0 ... 10.0
%
Overview parameter G
Parameter Function Parameter values Unit
G. OPEN Displacement of the upper stop with the following parameters:
G1.LEVEL1 Threshold 1 0.1 ... 1.0 ... 10.0
G2.LEVEL2 Threshold 2 0.1 ... 2.0 ... 10.0
G3.LEVEL3 Threshold 3 0.1 ... 4.0 ... 10.0
%