Operating instructions
Parameterizing/addressing
10.3 Overview of parameters
SIPART PS2 with and without HART communications
Operating Instructions, 09/2008, A5E00074631-08
143
Overview parameter H
Parameter Function Parameter values Unit
H. TMIN Monitoring of the lower limit temperature with the following parameters:
H1.TUNIT Temperature unit °C °F
H2.LEVEL1 Threshold 1 -40 ... -25 ... 90 -40 ... 194
H3.LEVEL2 Threshold 2 -40 ... -30 ... 90 -40 ... 194
H4.LEVEL3 Threshold 3 -40 ... 90 -40 ... 194
°C/°F
Overview parameter J
Parameter Function Parameter values Unit
J. TMAX Monitoring of the upper limit temperature with the following parameters:
J1.TUNIT Temperature unit °C °F
J2.LEVEL1 Threshold 1 -40 ... 75 ... 90 -40 ... 194
J3.LEVEL2 Threshold 2 -40 ... 80 ... 90 -40 ... 194
J4.LEVEL3 Threshold 3 -40 ... 90 -40 ... 194
°C/°F
Overview parameter L
Parameter Function Parameter values Unit
L. STRK Monitoring the path integral with the following parameters:
L1. LIMIT Limit for the number of changes of direction 1 ... 1E6 ... 1E8
L2.FACT1 Factor 1 0.1 ... 1.0 ... 40.0
L3.FACT2 Factor 2 0.1 ... 2.0 ... 40.0
L4.FACT3 Factor 3 0.1 ... 5.0... 40.0
Overview parameter O
Parameter Function Parameter values Unit
O. DCHG Monitoring the changes in direction with the following parameters:
O1.LIMIT Limit for the number of changes of direction 1 ... 1E6 ... 1E8
O2.FACT1 Factor 1 0.1 ... 1.0 ... 40.0
O3.FACT2 Factor 2 0.1 ... 2.0 ... 40.0
O4.FACT3 Factor 3 0.1 ... 5.0... 40.0










