Operating instructions
Parameterizing/addressing
10.4 Description of parameters
SIPART PS2 with and without HART communications
148 Operating Instructions, 09/2008, A5E00074631-08
9.SPRE - Split range end
With these two parameters in combination with parameter "7.SDIR", you can limit the
effective setpoint. This allows split range tasks with the following characteristic curves to be
solved:
● rising/falling
● falling/rising
● falling/falling
● rising/rising
3RVLWLRQHU
6',5 )$//
(QWLUHSRVLWLRQLQJUDQJH
3RVLWLRQHU
6',5 UL6(
635( 635$
3RVLWLRQHU
3RVLWLRQLQJUDQJH
3RVLWLRQHU
3RVLWLRQLQJUDQJH
635$
635(
>WR@
,:
\ [
Figure 10-2 Example: Split range operation with two positioners
The factory setting is "100".
10.4.2.4 Description of parameters 10 and 11
10.TSUP - Setpoint ramp OPEN
and
11.TSDO - Setpoint ramp CLOSED
The setpoint ramp is effective in automatic mode and limits the speed of change of the
effective setpoint. When switching from manual to automatic mode, the setpoint ramp is
used to adjust the effective setpoint to the setpoint occupied by the positioner.