3.3 Operation with natural gas
SIPART PS2 with and without HART communications
20 Operating Instructions, 09/2008, A5E00074631-08
3.2.2 Structure of the nameplate
II 2 G EEx ia/ib II C T6/T5/T4
Ta = -30 ... 50/65/80°C
Uh= 18...30V
Iw = 0/4...20mA
Siemens AG, D-76181 Karlsruhe
www.siemens.com/sipartps2
IP66
NEMA Type 4x
Made in France
TÜV 00 ATEX 1654
p = 1,4 ... 7bar
0044
F-Nr.: N1-S610-7534410
F-Nr.: N1-S610-7534410
Ta = -30 ... 50(T6)/65(T5)/80(T4) °C
Install per Contr. Dwg. A5E00065622D
CL I, DIV 2, GP ABCD T6/T5/T4
CL I, ZN 2, GP IIC T6/T5/T4
(IS) CL I, DIV 1, GP ABCD T6/T5/T4
(FM)/(CSA) CL I, ZN 1, AEx ib IIC / Ex ib IIC T6/T5/T4
$33529('
$33529('
FM
FM
IECEx TUN 04.0018 Ex ia/ib IIC T6..T1
Technical data and temperature classes see certificate
SIPART PS2 HART Positioner
206DR5 10-0EG00-0AA
Manufacturer Fabrication number
Product name Approvals
Order number Degree of protection
Technical data Consult operating instructions
Place of manufacture
Figure 3-5 Structure of the nameplate, example
3.3 Operation with natural gas
3.3.1 Safety notes for operation with natural gas
When operating the positioner with natural gas, you must follow and adhere to the following
safety notes:
WARNING
Operation with natural gas
1. Only the "EEx ia" version of the positioner and optional modules with the "EEx ia" type
of protection may be operated with natural gas. Positioners with other types of
protection, e.g. flameproof enclosure or versions for zones 2 and 22 are not permitted.
2. Do not operate the positioner with natural gas in closed spaces.
3. Natural gas is continuously blown off in the servo-drive depending on the model. Special
care must therefore be taken during maintenance activities near the positioner. Always
ensure that the immediate surroundings of the positioner are adequately ventilated.
4. The mechanical limit switch module may not be used when operating the positioner with
natural gas.
5. Depressurize the devices operated with natural gas adequately during maintenance
activities. Open the cover in an explosion-free atmosphere and depressurize the device
for at least two minutes.