Operating instructions
Alarm, error, and system messages
11.4 Fault correction
SIPART PS2 with and without HART communications
Operating Instructions, 09/2008, A5E00074631-08
199
11.4 Fault correction
11.4.1 Fault identification
Diagnostics guide
Fault See fault table
In which mode does a fault occur?
• Initialization
1
• Manual and automatic modes
2 3 4 5
In which environment and under which boundary conditions does a fault occur?
• Wet environment (e.g. strong rain or constant condensation)
2
• Vibrating (oscillating) control valves
2 5
• Impact or shock loads (e.g. vapor shocks or breakaway valves)
5
• Moist (wet) compressed air
2
• Dirty (contaminated with solid particles) compressed air
2 3
When does a fault occur?
• Regularly (reproducible)
1 2 3 4
• Sporadically (not reproducible)
5
• Mostly after a specific operation time
2 3 5
See also
Remedial measures table 1 (Page 200)
Remedial measures table 2 (Page 201)
Remedial measures table 3 (Page 201)
Corrective measures Table 4 (Page 202)
Remedial measures table 5 (Page 203)