Operating instructions

Alarm, error, and system messages
11.4 Fault correction
SIPART PS2 with and without HART communications
202 Operating Instructions, 09/2008, A5E00074631-08
Fault profile (symptoms) Possible cause Remedial measures
Pneumatic leakage in the positioner
- actuator system; start the leakage
test in "RUN 3" (initialization).
Rectify leakage in the actuator
and/or feed line.
In case of an intact actuator and
tight feed line: repair
1)
or a new
device
A piezo valve activates constantly in
the stationary automatic mode
(constant setpoint) and the manual
mode.
Dirt in the pneumatic block, see
above
See above
Fault table 3
1)
More information is given under the also-see link.
See also
Service and maintenance (Page 205)
11.4.5 Corrective measures Table 4
Symptoms Possible cause(s) Corrective measures
Sticking friction of the packing gland
from the control valve or actuator
too large
Reduce friction or increase dead
zone of positioner (parameter
"dEbA") until the oscillation stops.
Looseness (play) in the
positioner/actuator/control valve
system
Part-turn actuator: Check for firm
seating of set screw on coupling
wheel.
Linear actuator: Check for firm
seating of lever on positioner shaft.
Correct any other play between the
actuator and the control valve.
In stationary automatic mode
(constant setpoint) and in manual
mode, both piezo valves continually
switch alternately, and the actuator
oscillates around a mean value.
Actuator too fast Increase actuating times using
throttle screws.
If a quick actuating time is needed,
increase the dead zone (parameter
"dEbA") until the oscillation stops.
Positioner doesn't move control
valve to the stop (at 20 mA).
Supply pressure too low. Load on
the feeding controller or system
output is too low.
Increase supply pressure, insert
ballast converter
Select 3/4-wire mode
Error table 4
See also
Service and maintenance (Page 205)