Operating instructions

Description
3.4 Device components
SIPART PS2 with and without HART communications
30 Operating Instructions, 09/2008, A5E00074631-08
3.4.6 Restrictors
Note
The exhaust air valve is always open in the de-energized state.
Reduce the air output to achieve actuating times of T > 1.5 s for small actuators. Use
restrictors Y1 ① and Y2 ② for this purpose.
When turned clockwise, they reduce the air output and finally shut it off.
In order to set the restrictors, we recommend closing them and then opening slowly.
In case of double-acting valves, ensure that both restrictors have approximately the same
setting.
Figure 3-14 Restrictors
Restrictor Y1
Restrictor Y2, only in the version for double-acting actuators
Hexagon socket-head screw 2.5 mm
See also
Pneumatic connection in the flameproof enclosure (Page 26)
Sequence of automatic initialization (Page 114)