Operating instructions
Description
3.4 Device components
SIPART PS2 with and without HART communications
30 Operating Instructions, 09/2008, A5E00074631-08
3.4.6 Restrictors
Note
The exhaust air valve is always open in the de-energized state.
● Reduce the air output to achieve actuating times of T > 1.5 s for small actuators. Use
restrictors Y1 ① and Y2 ② for this purpose.
● When turned clockwise, they reduce the air output and finally shut it off.
● In order to set the restrictors, we recommend closing them and then opening slowly.
● In case of double-acting valves, ensure that both restrictors have approximately the same
setting.
Figure 3-14 Restrictors
① Restrictor Y1
② Restrictor Y2, only in the version for double-acting actuators
③ Hexagon socket-head screw 2.5 mm
See also
Pneumatic connection in the flameproof enclosure (Page 26)
Sequence of automatic initialization (Page 114)