Operating instructions

SIPART PS2 with and without HART communications
Operating Instructions, 09/2008, A5E00074631-08
35
Mounting
4
4.1 Safety notes for installation
WARNING
Mechanical impact effect
Protect the 6DR5**0-*G***-**** version of the positioner from mechanical impact effects that
are greater than 1 Joule; this ensure adherence to the IP66 degree of protection.
When installing, observe the following sequence imperatively to avoid injuries or
mechanical damage to the positioner/mounting kit:
1. Mount the positioner mechanically.
2. Connect the electrical auxiliary power supply.
3. Connect the pneumatic auxiliary power supply.
4. Commission the positioner.
WARNING
Assembling the components
When assembling components, ensure that only those positioners and optional modules
are combined with each other that are approved for the corresponding operating range.
This condition is particularly applicable for the safe operation of the positioner in the areas
of zones 1, 2 and 22, where the atmosphere may be potentially explosive. Observe the
device categories 2 and 3 of the device itself and its optional modules imperatively.
CAUTION
Humid environment/dry compressed air
Install the positioner in a humid environment such that the positioner shaft does not freeze
at low ambient temperatures.
Ensure that water does not seep through an open enclosure or an open gland. Water may
seep through if the positioner is not installed and connected on-site immediately and finally.
As a general rule, the positioner must be operated only with dry compressed air. Therefore,
use the customary water separator. An additional dryer is required in extreme cases. The
use of dryers is especially important when you operate the positioner at low ambient
temperatures. Set the Purge air switch to the "OUT" position when installing on the
pneumatic block, above the pneumatic connections.