Operating instructions

SIPART PS2 with and without HART communications
Operating Instructions, 09/2008, A5E00074631-08
71
Connection
6
6.1 Electrical connection
6.1.1 Safety notes for electrical connections
WARNING
Electrical connections in hazardous areas
Regulations in the test certificate applicable for your country must be followed.
National regulations and laws for hazardous areas applicable in your country must be
followed for electrical connections. In Germany, these are, e.g.:
Working reliability regulation
The regulation for setting up electrical plants in hazardous areas, EN 60079-14
(previously VDE 0165, T1)
The EC-type examination certificate
WARNING
If the intrinsically safe version is accidentally operated with a higher operating voltage, the
positioner may not be used in intrinsically safe applications any longer.
When used in areas having potentially explosive atmospheres, electrical auxiliary power
can be supplied to the positioners in flameproof enclosures only if the enclosure is closed
and the approved electronic unit has been installed. If required, we recommend checking
whether the available auxiliary power matches with the one specified on the nameplate and
in the test certificate applicable for your country.
In case of flameproof enclosures, the duct openings for electronic connections must be
closed with Ex d certified cable entries or Ex d certified sealing plugs, or, if using the
conduit piping system, an ignition trap must be set up at a maximum distance of 46 cm
(18") from the enclosure.
WARNING
Assembling the components
When assembling components, ensure that only those positioners and optional modules
are combined with each other that are approved for the corresponding operating range.
This condition is particularly applicable for the safe operation of the positioner in the areas
of zones 1, 2 and 22, where the atmosphere may be potentially explosive. Observe device
categories 2 and 3 of the device itself and its optional modules implicitly.