Operating instructions

SIPART PS2 (6DR5...)
22 A5E03436620-04, 02/2014
4.3.2
Pneumatic connection in the flameproof enclosure
Structure
The pneumatic connections are provided on the right side of the positioner.
Restrictor Y2
*)
Actuating pressure Y1
Restrictor Y1
Exhaust air outlet
Actuating pressure Y2
*)
Enclosure ventilation (2x)
Supply air P
Z
*) for double-acting actuators
Figure 4-12 Pneumatic connection in the flameproof enclosure
4.4
Restrictors
Reduce the air output to achieve actuating times of T > 1.5 s for small actuators. Use restrictors Y1 and Y2 for this
purpose.
When turned clockwise, they reduce the air output and finally shut it off.
In order to set the restrictors, we recommend closing them and then opening slowly.
In case of double-acting valves, ensure that both restrictors have approximately the same setting.
Restrictor Y1
Restrictor Y2, only in the version for double-acting actuators
Hexagon socket-head screw 2.5 mm
Figure 4-13 Restrictors