Operating instructions
SIPART PS2 (6DR5...)
A5E03436620-04, 02/2014
25
5.3
Sequence of automatic initialization
See detailed operating instructions for information on sequence of automatic initialization.
5.4
Parameter
Introduction
Parameters 1 to 5 are the same for all versions of positioner. These parameters are used to adjust the positioner to the
actuator. Normally the parameter setup is sufficient to be able to operate the positioner on an actuator.
If you want to get to know the positioner in detail, gradually try out the effects of the remaining parameters by systematic
testing
Note
Factory
-set parameter values are printed in bold in the following table.
Overview
Parameter
Function
Parameter values
Unit
1.YFCT
Type of position actuator
turn (part-turn actuator)
WAY (linear actuator)
LWAY (linear actuator without sine correction)
ncSt (part-turn actuator with NCS)
-ncSt (part-turn actuator with NCS, inverse
direction of action)
ncSL (linear actuator with NCS)
ncSLL (linear actuator with NCS and lever)
2.YAGL
Nominal angle of rotation of the feedback message
1)
33°
Degrees
90°
3.YWAY
2)
Range of stroke (optional setting)
3)
OFF
mm
5 | 10 | 15 | 20
(Short lever 33°)
25 | 30 | 35
(Short lever 90°)
40 | 50 | 60 | 70 | 90 | 110 | 130
(Long lever 90°)
4.INITA
Initialization (automatic)
NOINI | no / ###.# | Strt
5.INITM
Initialization (manual)
NOINI | no / ###.# | Strt
1)
Set the transmission ratio selector accordingly.
2)
The parameter only appears for "WAY" and for "ncSLL".
3)
When used the value must correspond with the set range of stroke on the actuator.
Carriers must be scaled to the actuator's stroke value,or if this is not scaled they then must be set to the next
largest scaled value.