Pneumatic data
Air exhaust valve (depressurize drive)
1
)
2 bar (29 psi)
8.2 Nm³/h (36.1 USgpm)
4 bar (58 psi)
13.7 Nm³/h (60.3 USgpm)
6 bar (87 psi)
19.2 Nm³/h (84.5 USgpm)
Valve leakage
< 610
-4
Nm³/h (0.0026 USgpm)
Throttle ratio
Adjustable up to ∞: 1
Auxiliary power consumption in the controlled state
< 3,6⋅10
-2
Nm³/h (0.158 USgpm)
1)
When using device version Ex d (6DR5..5-...), values are reduced by approximately 20%.
7.1.3
Constructional design
7.1.4
Controller
Controller
Control unit
Five-point controller
Adaptive
Dead zone
dEbA = auto
Adaptive or can be preset
dEbA = 0.1 ... 10 %
Adaptive or can be preset
Analog-to-digital converter
Scanning time
10 ms
Resolution
0.05 %
Transmission error
0.2 %
Temperature influence
0.1 %/10 K (≤ 0.1 %/18 °F)
Cycle time
20 mA/HART device
20 ms
PA device
60 ms
FF device
60 ms (min. loop time)
7.2
Natural gas as actuator medium
See detailed operating instructions for technical data for natural gas as actuator medium.