Operating instructions
SIPART PS2 (6DR5...)
A5E03436620-04, 02/2014
45
Additional modules
Without Ex protection
With Ex protection
Ex "ia"
With Ex protection
Ex "ic", "nA"
● Storage
1K5, but -40 to +90 °C (1K5, but -40 to +176 °F)
● Transport
2K4, but -40 to +90 °C (2K4, but -40 to +176 °F)
Vibration resistance
● Harmonic oscillations
(sine wave) according to
IEC 60068-2-6
3.5 mm (0.14"), 2 ... 27 Hz, 3 cycles/axis
98.1 m/s² (321.84 ft/s²), 27 ... 300 Hz, 3 cycles/axis
●
Permanent shocks according to
IEC 60068-2-29
300 m/s
2
(984 ft/s
2
), 6 ms, 4000 shocks/axis
Torque for cable gland nut made of
Plastic
Metal
Stainless steel
2.5 Nm (1.8 ft lb)
4.2 Nm (3.1 ft lb)
4.2 Nm (3.1 ft lb)
Housing protection type
IP68 according to EN 60529; NEMA 4X / Encl. Type 4X
For connecting to circuits with the
following peak values
- U
i
= 5 V
I
i
= 160 mA
P
i
= 120 mW
U
i
= 5 V
Effective internal capacitance
-
C
i
= 180 nF
C
i
= 180 nF
Effective internal inductance
-
L
i
= 922 μH
L
i
= 922 μH
Certificates and approvals
CE conformity The applicable directives and standards applied with their revision levels can be
found in the EC declaration of conformity on the Internet.
Explosion protection
Types of protection
Ex markings
ATEX/IECEx
FM
● Intrinsic safety "ia"
Zone 1:
II 2 G Ex ia IIC T6/T4 Gb
IS, Class I, Divison 1, ABCD
IS, Class I, Zone 1, AEx ib, IIC
●
Intrinsic safety "ic"
Zone 2:
II 3 G Ex ic IIC T6/T4 Gc
-
● Non-sparking "nA"
Zone 2:
II 3 G Ex nA IIC T6/T4 Gc
NI, Class I, Divison 2, ABCD
NI, Class I, Zone 2, AEx nA, IIC
Permissible ambient temperature
T4: -40 ... +90 °C (-40 ... +194 °F)
T6: -40 ... +70 °C (-40 ... +158 °F)
T4: -40 ... +85 °C (-40 ... +185 °F)
T6: -40 ... +70 °C (-40 ... +158 °F)
7.5.7
External position sensing system
7.5.7.1
Operating conditions for all device versions
Ambient temperature In hazardous areas, observe the maximum permissible
ambient temperature corresponding to the temperature
class.
● Permissible ambient temperature for operation
-40 ... +90 °C (-40 ... +194°F)
Degree of protection
1)
IP66 according to EN 60529 / NEMA 4X
Climate class
According to DIN EN 60721-3-4
● Storage
1K5, but -40 ... +90 °C (1K5, but -40 ... +194 °F)
● Transport
2K4, but -40 ... +90 °C (2K4, but -40 ... +194 °F)
● Operation
4K3, but -40 ... +90 °C (4K3, but -40 ... +194 °F)
1
) Impact energy max. 1 joule.