Constructional design for all device versions
How does it work?
Range of stroke (linear actuator)
3 ... 130 mm (0.12 ... 5.12") (angle of rotation of the
positioner axis 16 to 90°)
Angle of rotation (part-turn actuator)
30 ... 100°
Mounting method
On the linear actuator
Using the mounting kit 6DR4004-8V and, if required, an
additional lever arm 6DR4004-8L on the actuators as per
IEC 60534-6-1 (NAMUR) with a fin, columns, or a plane
surface.
On the part-turn actuator
Using the mounting kit 6DR4004-8D on the actuators with
fastening plane as per VDI/VDE 3845 and IEC 60534-6-2:
The required mount must be provided on the actuator-
side.
Material
Enclosure
Makrolon® glass-fiber reinforced polycarbonate (PC)
Weight, basic device
Approximately 0.9 kg (1.98 lb)
Torque for plastic cable gland nut
2.5 Nm
7.5.7.3
Certificates, approvals, explosion protection for all device versions
Electrical data
For connecting to circuits with the
following peak values
U
i
= 5 V
I
i
= 100 mA
P
i
= 160 mW
C
i
= negligibly small
L
i
= negligibly small
Certificates and approvals
CE conformity The applicable directives and standards applied with their revision levels can
be found in the EC declaration of conformity on the Internet.
Explosion protection
Ex markings
Explosion protection in accordance with
ATEX
Intrinsic safety "ia"
Zone 1:
II 2 G Ex ia IIC T6/T4 Gb
Zone 21:
II 2 D Ex ia IIIC 110°C Db
Intrinsic safety "ic"
Zone 2:
II 3 G Ex ic IIC T6/T4 Gc
Non-sparking "nA"
Zone 2:
II 3 G Ex nA IIC T6/T4 Gc
Permissible ambient temperature
T4: -40 ... +90 °C (-40 ... +194 °F)