4 Sequences
4.1 Instruction parameters
COMMAND DESCRIPTION PARAMETERS
CALL Calls an other sequence and returns
control to the calling sequence
called sequence number parameters
from 1 to 7
COM Send command subsystem command number parameters
from 1 to 5
CSEQ Initiate another sequence sequence number
DECP Decrement point value of 1 unit subsystem point treatment code
ENDIF End of IF block none none none
FOR Executes n times the instructions before
the NEXT statements
cycle variable (acceptable
values are -4, -3, -2)
initial value
0 - 65535
final value 0
- 65535
step value 0 -
65535
IFEQ Test for equality (IF Equal) subsystem point value relative point
offset
IFGT Test for greater size (IF Greater Than) subsystem point value relative point
offset
IFLT Test for smaller size (IF Less Than) subsystem point value relative point
offset
IFNE Test for inequality (IF Not Equal) subsystem point value relative point
offset
INCP Increment point value of 1 unit subsystem point treatment code
NEXT Ends a FOR loop none none none
NOP No operation none none none
SETP Set point (assign a specific value to a
point)
subsystem point value treatment
code
STOP End of sequence none none none
WAIT Pause minutes seconds
Tab. 51