11 Point List for Subsystems
11.1 WARNING (Type 0, Subtypes 0-7)
No. Definition
Points from 1 to 100 do not have a predefined description
11.2 CZ10 (Type 1, Subtypes 0-7)
No. Definition
1 GATEWAY CONNECTION STATUS
2 SUBSYSTEM OPERATIVE STATUS
3 SPARE
4 CONTROL SECTOR FAULT STATUS
5 CENTRAL POWER SUPPLY STATUS
6 TELETRANSMISSION FAULT
7 TELETRANSMISSION ALARM
8 FIRE ALARM STATUS
9 MAINTENANCE
10 DAY/NIGHT ORGANIZATION OF FIRE SECTOR
11 PART OF FIRE SECTOR EXCLUDED
12 FIRE SECTOR FAULT STATUS
13 EXTERNAL FAULT STATUS OF FIRE SECTOR
14 EXTERNAL ALARM STATUS OF FIRE SECTOR
15 PART OF CONTROL SECTOR EXCLUDED
16-39 GROUPS 1-24
40-63 GROUPS 25-48
64-87 GROUPS 49-72
88-111 GROUPS 73-96
112 PART OF EXTINGUISHING SECTOR EXCLUDED
113 PART OF GAS SECTOR EXCLUDED
114-121 EXTINGUISHING/GAS ALARMS STATUS FOR LINES 1-8
122-129 SPARES
130-137 EXTINGUISHER CHARGE STATUS FOR LINES 1-8
138-145 EXTINGUISHER CHARGE MODE FOR LINES 1-8
146-153 EXTINGUISHER CHARGE SUPERVISION ON LINES 1-8
154-161 EXTING/GAS FAULT STATUS OF LINES 1-8
162 TECHNOLOGICAL ALARM STATUS
163 SPARES
164 DAY/NIGHT ORGANIZATION OF TECHNOLOGICAL SECTOR
165 PART OF TECHNOLOGICAL SECTOR EXCLUDED
166 TECHNOLOGICAL SECTOR FAULT STATUS
167 EXTERNAL FAULT STATUS OF TECHNOLOGICAL SECTOR
168-263 DIGITAL INPUTS 1-96
264-663 ELEMENTS 1-50 ON LINES 1-8
664-1063 ELEMENTS 1-50 ON LINES 9-16
1064-1463 ELEMENTS 1-50 ON LINES 17-24
Note: There are eight subtypes of the CZ10 subsystem:
Subtype 0 contains points 1-39
Subtype 1 contains points 1-63
Subtype 2 contains points 1-87
Subtype 3 contains points 1-111
Subtype 4 contains points 1-263
Subtype 5 contains points 1-663
Subtype 6 contains points 1-1063
Subtype 7 contains all the 1463 points shown above.