12.15 CC-11
Code no. Code description Parameter
0 STATUS REQUEST
1 ACK. GENERAL ALARM + LOCAL ALARM FOR ALL AREAS
2 RESET GENERAL ALARM + LOCAL ALARM FOR ALL AREAS
3 ACK. GENERAL ALARM AND LOCAL ALARM
FOR SPECIFIED AREA
point #
4 RESET GENERAL ALARM AND LOCAL ALARM
FOR SPECIFIED AREA
point #
5 SWITCH OFF ALARM RT DELAY point #
6 SET AREA TO NIGHT point #
7 SET AREA TO DAY point #
8 INCLUDE ALL SECTIONS WITHIN SPECIFIED AREA point #
9 EXCLUDE ALL SECTIONS WITHIN SPECIFIED AREA point #
10 SET ALL SECTIONS WITHIN SPECIFIED AREA TO TEST point #
11 INCLUDE SECTION point #
12 EXCLUDE SECTION point #
13 SET SECTION TO TEST point #
14 ACK. SECTION point #
15 RESET SECTION ALARM point #
16 DISABLE EXTINGUISHING SECTION RELEASE point #
17 DISABLE EXTINGUISHING SECTION AUTOMATIC RELEASE point #
18 ENABLE EXTINGUISHING SECTION RELEASE point #
19 ACK. ZONE point #
20 RESET ZONE ALARM point #
21 INCLUDE ZONE point #
22 EXCLUDE ZONE point #
23 SET ZONE TO TEST point #
24 SET ZONE TO RENOVATION point #
25 SET ZONE TO INSTALLATION TEST point #
26 ZONE RENOVATION OFF point #
27 ZONE INSTALLATION TEST OFF point #
28 DEACTIVATE CONTROL ZONE point #
29 ACTIVATE CONTROL ZONE point #
30 INCLUDE ALL ELEMENTS WITHIN SPECIFIED ZONE point #
31 INCLUDE ELEMENT point #
32 EXCLUDE ELEMENT point #
33 ACK. ELEMENT FAULT point #
34 DEACTIVATE CONTROL OUTPUT ELEMENT point #
35 ACTIVATE CONTROL OUTPUT ELEMENT point #
36 ACK. FUNCTION UNIT FAULT point #
37 RESET FUNCTION UNIT ALARM point #
38 ACK. CONTROL UNIT FAULT point #
39 ACK. POWER SUPPLY FAULT point #
40 ACK. TERMINAL FAULT point #
41 ACK. REMOTE TRANSM. DEVICE FAULT point #
42 ACK. REMOTE TRANSM. (ALARM) FAULT point #
43 ACK. REMOTE TRANSM. (FAULT) FAULT point #
44 ACK. REMOTE TRANSM. (OTHER) FAULT point #
45 ACK. INTERN. HORN FAULT point #
46 ACK. EXTERN. HORN FAULT point #
47 DEACTIVATE EXTERNAL HORN point #
48 ACTIVATE EXTERNAL HORN point #
49 INCLUDE EXTERNAL HORN point #
50 SET SECTION TO INSTALLATION TEST point #
51 SET SECTION TO RENOVATION point #
52 EXCLUDE AUTO ZONE BELONGING TO THE SECTION point #
53 ACK. (ALARM) FAULT LSE point #
54 ALARM RESET LSE point #
55 ACK. (ALARM) FAULT FSK point #
56 ALARM RESET FSK point #
57 INTERNAL HORN OFF point #
58 EXTERNAL HORN OFF point #
59 ACK. MULTI DEVICE point #
60 ACK. LON DEVICE point #
61 FUNCTION UNIT OFF point #
62 FUNCTION UNIT ON point #
63 ACK. NETWORK FAULT point #
Notes:
the point number is the relative point number of CC-11 in LMS
LSE is the standard extinguishing interface
FSK is the fire brigade key box