Instruction manual

Page 124 SITRANS LR 300 – INSTRUCTION MANUAL 7ML19985CL02
mmmmm
Appendix VII
Physical Block 1
This is the only physical block for the device.
Relative
Index
Name
Internal Product Parameter or
Constant Value
Description
Data Type
& size
0 BLOCK OBJECT Refer to Sections 3.4 & 3.7.2
in Profi. Spec.
Record
1 ST_REV Static revision –
incremented by
configuration device
Uint16,
eeprom
2 TAG_DESC E781- PAR_HART_LONG_TAG Tag Name for device,
supplied by the master
String [32]
eeprom
3 STRATEGY PAR_PROFI_STRATEGY Uint16
4 ALERT_KEY PAR_PROFI_ALERT_KEY Uint8
5 TARGET_MODE Target mode for block Uint8
6 MODE_BLK 3 bytes
actual, permitted, normal
Bits
7– out of service
6–init. Manual,not class a/b
5- local override, not class A
4- manual
3- automatic
2- cascade, not class a/b
1-Remote cascade
0- remote output not a/b
Record
7 ALARM_SUM Summary of alarms Record
8 SOFTWARE_REVISION P900-1, PAR_SOFTWARE_REV Software rev. String, 16
9 HARDWARE_REVISION P900-2, PAR_SOFTWARE_REV Hardware board stack String, 16
10 DEVICE_ MAN _ID 0x58 Manufacturer ID Uint16
11 DEVICE_ID “IQ300” ID indicating IQ300 String, 16
12 DEVICE_SER_NUM PAR_SERIAL_NUMBER_BATCH
(Drops first 5 characters of serial
number)
Serial number String, 16
13 DIAGNOSIS PAR_DIAGNOSTIC_STATE
Point 1
Diagnostic – see Page 72,
3.11.4
Uint8, 4
bytes in
total
14 DIAGNOSIS_EXTENSION PAR_DIAGNOSTIC_STATE
Point 2
Device specific diagnostics,
Failsafe, LOE, short, stack
overflow
Not
used
15
Not
used
16
17 DEVICE_CERTIFICATION Based on Item number
18 WRITE_LOCKING P000, P799 Controls write access, 0 –
no writes, 2457 – writes
allowed
Uint16
SITRANS LR 300.book Page 124 Monday, June 10, 2002 7:18 PM