Instruction manual

Page 34 SITRANS LR 300 – INSTRUCTION MANUAL 7ML19985CL02
mmmmm
Interconnection
SITRANS LR 300 Wiring
Notes
Installation shall only be performed by qualified personnel and in accordance with
local governing regulations.
The equipment must be protected by a 15 A fuse or circuit breaker in the building
installation.
The circuit breaker or switch in the building installation, marked as the disconnect
switch, shall be in close proximity to the equipment and within easy reach of the
operator.
Do not use a Ground Fault Interrupt (G.F.I.) with the SITRANS LR 300. The ground path
is used for filtering purposes in conjunction with the universal power supply.
All Input/Output wiring must be shielded for CE compliance, except for supply voltage.
All field wiring must have insulation suitable for the applied input
voltage.
WARNING: Avoid static discharge to terminals.
1
3
4
7
5
6
2
A
R
S
4
8
5
B
COM
L2/N
L1/+
OI
Supply voltage AC or DC
Shield, installed on
IS version only
RS-485
Modbus, or Dolphin
protocol
HART/mA or
Profibus-PA
SITRANS LR 300.book Page 34 Monday, June 10, 2002 7:18 PM