Instruction manual

Page 52 SITRANS LR 300 – INSTRUCTION MANUAL 7ML19985CL02
mmmmm
Applications
Application Example: Sliding Waveguide on Anaerobic
Digesters
Run: To start normal operation, press the PROGRAM key .
Parameter Enter
P999 ---- master reset
P001 1 mode of measurement = level
P002 1 material = liquid
P003 2 measurement response = 1m/minute
P004 240 antenna = factory
P005 1 units = meters
P006 10 empty distance = 10m
P007 8 span = 8m
P820 8 algorithm = bLF (best of Largest or First)
P830 7 TVT type = factory
P837/838
(Note above)
2 & 1 Auto False Echo Suppression
Notes:
Only set P837 if the product is at least 2m (78”) away from the flange face. If it is
closer, leave P837 at 1 until the level drops and the distance increases beyond
2m (78”).
P007
P006
Horn
The raised position is for installation and
maintenance. The lowered position is for
operation. Program the unit for operation
in the lowered position.
This application is to obtain a level
measurement and corresponding 4-20 mA
output proportional to the sludge level on
a digester. The bottom of the
SITRANS LR 300 mounting flange is 10m
from the bottom of the digester when the
SITRANS LR 300 is lowered to its normal
operating position.
The empty level is 0m (bottom) and the full
level (span) is 8m from the bottom. The
maximum rate of filling or emptying is
SITRANS LR 300.book Page 52 Monday, June 10, 2002 7:18 PM