Parameters
P712 Echo Lock Sampling
Sets the number of consecutive echoes appearing above or below the echo currently
locked onto. Sampling ratio must occur before the measurements are validated as the
new reading (for Echo Lock P711 values:
1
or
2
).
Example Settings:
P711 = 2: material agitator
P712 = 5:2
Example Results:
A new reading will not be validated unless 5 consecutive measurements higher or 2
consecutive measurements lower than the current reading occur.
P713 Echo Lock Window (F = 0.0000)
Adjusts the new measurement changes permitted before the Echo Lock is applied.
The Echo Lock Window is a “distance window” (Units, P005) centered on the echo and
used to derive the reading. When a new measurement is in the window, the window is
re-centered and the new reading calculated. Otherwise, the new measurement is verified
by Echo Lock (P711) before the reading is updated.
Values
Range: 1:1 to 99:99
Format: xx:yy
xx = the number of
above echoes
yy = the number of
below echoes
Related Parameter
P711 Echo Lock
P711 value P712 pre-set value
1: maximum verification 5:5
2: material agitator 5:2
Values
Range: 0.0000 to 99999
Pre-set: 0.0000
Altered by
P711 Echo Lock
Related Parameters
P005 Units
Note: Resetting P711 returns P712 to the respective pre-set values.