Data Sheet for Product

21
Siemens CM1N4561en
Smart Infrastructure 2021-06-21
Electrical connections and connecting cable
Wire cross-sectional area 0.5...2.5 mm
2
, AWG 21...14
3)
Cable entries 4 x M20 (
20.5 mm)
With knockouts for standard ½"
conduit connectors (
21.5 mm)
Mit Ausbrechöffnungen für ½" Schlauchverbindungen
(
21,5 mm)
SKD62/MO Fixed connection cable
Cable length 0.9 m
Number of cores 5 x 0.75 mm
2
Degree and class of protection
Protection class As per EN 60730
Automatic action Typ 1AA / Typ 1AC / Modulation Action
Pollution degree 2
Housing protection upright to sideways IP 54 as per EN 60529
Environmental conditions
Operation IEC 60721-3-3
Climatic conditions Class 3K5
Temperature, general -15...<50 °C
Humidity (non-condensing) 5...95 % r.h.
Transportation IEC 60721-3-2
Climatic conditions Class 2K3
Temperature -30...65 °C
Humidity (non-condensing) 5...95 % r.h.
Storage IEC 60721-3-1
Climatic conditions Class 1K3
Temperature -15...50 °C
Humidity (non-condensing) -5...95 % r.h.
Directives and standards
Product standarad EN 60730-x
Electromagnetic compatibility (Applications) For use in residential, commerical, and industrial
environments
EU conformity (CE) A5W00007752
4)
RCM conformity A5W00007898
4)
EAC conformity Eurasia conformity for all SKD..
UL, cUL AC 230 V -
AC 24 V UL 873 http://ul.com/database
Environmental compatibility
The product environmental declarations CE1E4561enX1 (SKD3.., SKD8..)
4)
, CE1E4561enX2 (SKD6..)
4)
and
A6V101083254 (external Modbus converter)
4)
contain data on RoHS compliance, materials composition,
packaging, environmental benefit and disposal.